Section 68 of Occupational Safety and Health Act CAP 236A: Steam receivers and steam containers
(1) Every steam receiver and all its fittings shall be of good construction, sound material, adequate strength, and free from patent defect, and shall be properly maintained.
(2) Every steam receiver, not so constructed and maintained as to withstand with safety the maximum permissible working pressure of the boiler or the maximum pressure which can be obtained in the pipe connecting the receiver with any other source of supply, shall be fitted with—
(a) a suitable reducing valve or other suitable automatic appliance to prevent the safe working pressure of the receiver being exceeded;
(b) a suitable safety valve so adjusted as to permit the steam to escape as soon as the safe working pressure is exceeded, or a suitable appliance for cutting off automatically the supply of steam as soon as the safe working pressure is exceeded;
(c) a correct steam pressure gauge, which shall indicate the pressure of steam in the receiver in kilograms per square centimetre;
(d) a suitable stop valve;
(e) except where only one steam receiver is in use, a plate bearing a distinctive number which shall be easily visible,
and the safety valve and pressure gauge shall be fitted either on the steam receiver or on the supply pipe between the receiver and the reducing valve or other appliance to prevent the safe working pressure being exceeded.
(3) For the purposes of paragraphs (a), (b), (c) and (d) of subsection (2), any set of receivers supplied with steam through a single pipe and forming part of a single machine may be treated as one receiver, and for the purpose paragraphs (a), (b) and (c) of subsection (2), any other set of receivers supplied with steam through a single pipe may be treated as one receiver:
Provided that this subsection shall not apply to any such set of receivers unless the reducing valve or other appliance to prevent the safe working pressure being exceeded is fitted on the said single pipe.
(4) Every steam receiver and all its fittings shall be thoroughly examined by an approved person, so far as the construction of the receiver permits, at least once in every period of twenty-four months or after repairs.
(5) A report of the result of every examination referred to in subsection (4), shall be in the prescribed form containing the prescribed particulars, including particulars of the safe working pressure and shall be entered in or attached to the general register, shall be signed by the person who carried out the examination.
(6) No steam receiver which has previously been used shall be taken into use in any workplace for the first time in that workplace until it has been examined and reported on in accordance with subsections (4) and (5).
(7) No new steam receiver shall be used in a workplace for the first time unless there has been obtained from the manufacturer of the receiver, or from a person approved by the Director, a certificate specifying the safe working pressure of the receiver stating the nature of the tests to which the receiver and fittings have been submitted, and the certificate is kept available for inspection, and the receiver is so marked as to enable it to be identified as the receiver to which the certificate relates.
(8) No person shall use, in any workplace, a steam receiver, or a steam container which does not comply with the standards set out in this section.
(9) Every steam container shall be so maintained as to secure that the outlet is at all times kept open and free from obstruction.
(10) In this section—
“approved person” means any person who is approved by the Director, by certificate in writing, to carry out examinations of steam receivers in accordance with, and for the purposes of, this section and to issue the certificate referred to in subsection (6);
“maximum permissible working pressure” has the same meaning as in section 67;
“safe working pressure” means, in the case of a new steam receiver, that specified in the certificate referred to in subsection (6) and, in the case of a steam receiver which has been examined in accordance with the provisions of this section, that specified in the report of the last examination;
“steam container” means any vessel, other than a steam pipe or coil, constructed with a permanent outlet into the atmosphere or into a space where the pressure does not exceed atmospheric pressure, and through which steam is passed at atmospheric pressure, or at approximately that pressure, for the purpose of heating, boiling, drying, evaporating or other similar purpose;
“steam receiver” means any vessel or apparatus other than a steam boiler, a steam container, a steam pipe or coil, or a part of a prime mover used for containing steam under pressure greater than atmospheric pressure.
Check the current authoritative text and amendment history before relying on this provision.